POWER MANAGEMENT CONTROL OF A HYBRID PV-GENSET SYSTEM USING ZELIO LOGIC SMART RELAY

Soeprapto Soeprapto, Unggul Wibawa, Mahfudz Shidiq

Abstract


Power management control using Zelio Logic Smart Relay is applied as a means to make automatic power transition from battery to generator and vice versa. The design of a hybrid system in a laboratory scale is described including the design of software part using Zelio Soft2 (ANONIM 3, 2014). The experiment results show that the values of voltage and power output of the solar cell will increase with the increasing intensity of the sun, while the current will be decreasing. The current sensor used in the system is able to detect the linear changes of current flowing into the load and to respond in a form of voltage to be inputted into Zelio. The automatic operation of genset can be performed properly and the SFC optimum value of the genset of 2.8 kW, 220 V, 50 Hz is 0.67 l/kWh under 72% loading of the generator capacity. Automatic switching of the hybrid system can be realized based on the sensing results of battery voltage and load voltage with the help of Zelio. Load is supplied through the battery inverter when the battery voltage exceeds its voltage, it is supplied directly from the genset and the relay is activated to charge the battery.


Full Text:

PDF

References


ANONIM1. (T.t.). Solar Power Medium-Large Scale (Hybrid-Grid Interractive). (PT. Azet Surya Lestari) Retrieved 6 April 2014, from http://www.azetsurya.com

ANONIM2. 2010. 5A Non-Invasive AC Current Sensor Module. Accessed July 26, 2014, from http://www.vcc2gnd.com

ANONIM3. (T.t.). Smart Relays. Accessed March 17, 2014, from Schneider Electric: http://www.schneider-electric.ca

ANONIM4. 2003. Analog Device-Low Cost Low Power Instrumentation Amplifier AD620. Catalog book

FITRIANA, I. 2003. Sustainable Energy Systems and Management (SESAM), MSc. Thesis. Flensburg.

HANSEN, A. D. et al. 2000. Model for a Stand- Alone PV System. Roskilde: Riso National Laboratory.

KARIANA, A. (T.t). Characteristics Study of Current-Voltage (IV curve) in Single Cells polycrystalline silicon as well as modeling. Proceedings of the Scientific Meeting of Central Java and Yogyakarta HFI XXV, XXV, pp. 163-166. DIY.

SIAHAAN, P. 2013. Performance Testing Generator Power Plant Biogas from Wastewater mills. SINGUDA ENSIKOM, 3 (1), 23-28.

SUMANTO. 1996. Synchronous machine. Yogyakarta: Andi.

TRIHADI, S. 2000. Draft Technical and Implementation of Power Systems Hybrid PV-Diesel in Sulawesi. Scientific Journal of Energy Technology.




DOI: http://dx.doi.org/10.21776/ub.jeest.2016.003.01.2

Refbacks

  • There are currently no refbacks.


Creative Commons License
This work is licensed under a Creative Commons Attribution 4.0 International License.